Time Mark 2744-120

3PH Ovr Cur, 120VAC, SPDT, (98075801) | Time Mark Corporation 2744-120
Datasheet

Price and Stock

Authorized Distributors
Non-Authorized Stocking Distributors
Non-Authorized Dealers

Documents

Download datasheets and manufacturer documentation for Time Mark 2744-120.

RS (Formerly Allied Electronics)
Datasheet2 pages12 years ago

Engineering Resources

View Evaluation kits and Reference designs for Time Mark 2744-120.

Descriptions

Descriptions of Time Mark 2744-120 provided by its distributors.

3PH Ovr Cur,120VAC, SPDT,(98075801) | Time Mark Corporation 2744-120
The Model 2744 3-Phase Over Current Monitor is designed to monitor the current level of a three-phase line or to compare the currents of three single-phase lines. If one or more current inputs rises above the trip level after the start delay has expired, the internal relay will de-energize. An adjustable start delay of 5 to 15 seconds will prevent nuisance tripping on start up. The current trip point is adjustable from 1 to 5 amps, and matching current transformers are available to extend the current range of the monitor. The Model 2744 will automatically reset when the current fault is corrected. An external manual reset can be added by installing a normally closed switch between the terminals marked RESET.
Time Mark

Manufacturer Aliases

Time Mark has several brands around the world that distributors may use as alternate names. Time Mark may also be known as the following names:

  • Time Mark Corporation
  • TIME MARK CORP SIGNALINE

Documents

Download datasheets and manufacturer documentation for Time Mark 2744-120.

RS (Formerly Allied Electronics)
Datasheet2 pages12 years ago