UPS Type = Double Conversion Online / Outputs = 9 / Input Voltage V = 120 / Output Voltage V = 120 / Rated Power kW = 2.7 / Operating Frequency Min. Hz = 40 / Operating Frequency Max. Hz = 70 / Backup Time min = 3 / Input Connection Type = NEMA L5-30P / Output Connection Type = US Type B (NEMA 5-20) Socket / Output Connection Type = NEMA L5-30R / UPS Interfaces = RJ45 Serial / UPS Interfaces = SmartSlot / UPS Interfaces = USB / Efficiency % = 91.5 / Mounting Type = Rack Mount / Protection Rating = IP20 / Operating Temperature Min. °C = 0 / Operating Temperature Max. °C = 40 / Width mm = 432 / Depth mm = 635 / Height mm = 85