유통업체에서 제공한 Phoenix Contact 2864273에 대한 설명입니다.
SIGNAL CONDITIONING, TEMPERATURE TRANSDUCER 1 MA INPUT,0-20 MA OUTPUT, DIP SWITCH
Temperature Sensor Modules MINI MCRSLPT100UINC TEMP TRANS -PT100
MCR temperature transducer for Pt 100 temperature sensors, configured via DIP switches, with screw connection, not preconfigured
Phoenix Contact Temperature Converter; MINI MCR-SL-PT100-UI-NC; RTD IN; 0 - 10V OUT; 0 - 20mA OUT; 1 Output; 24VDC; Configurable Signal
RTD TRANSDUCER, 24VDC, DIN RAIL; Signal Conditioner Input:Pt100; Signal Conditioner Output:Current, Voltage; No. of Output Channels:1Channels; Accuracy %:-; Output Accuracy:-; Supply Voltage:24VDC; No. of Channels:1 Chan
TEMPERATURE TRANSDUCER; Operating Temperature Min: -20°C; Operating Temperature Max: 65°C; SVHC: No SVHC (15-Jan-2018); Approval Bodies: CE, GL, UL; External Depth: 102.5mm; External Length / Height: 93.1mm; External Width: 6.2mm; Input Type: RTD; No. of Outputs: 1Outputs; Safety Category: ATEX II 3 G Ex nA II T4 X; Wire Size AWG Max: 26AWG; Wire Size AWG Min: 12AWG
Analogue Input Type = 1 mA / Analogue Output Type = 0/4 ... 20 mA / Analogue Output Type = 20 ... 0/4 mA / Analogue Output Type = 0/1 ... 5 V / Analogue Output Type = 0 ... 10 V / Analogue Output Type = 10 ... 0 VDC / Temperature Measuring Range Min. °C = -150 / Temperature Measuring Range Max. °C = 850 / Operating Voltage Min. V = 19.2 / Operating Voltage Max. V = 30 / Resistance Thermometer Input Type = Pt100 / Isolation Input Type = 3-Way / Channels = 1 / Current Output Impedance Ohm = 500 / Accuracy % = 0.2 / Electrical Isolation = Yes / Cross-Section mm² = 2.5 / Mounting Type = DIN Rail Mount / Protection Rating = IP20 / Series = MINI MCR